The object of this paper is to emphasize the importance of the representation of the core configuration when seeking transients developed in a distribution transformer under an unbalanced situation. Digital time-domain simulations are performed with the Alternative Transients Program (ATP) for the case of a distribution three-phase transformer using the following two core configuration representations available in the ATP: three-legged core form and fivelegged core. Severe overvoltages and high saturated currents would not be evidenced if the wrong core configuration representation was used during simulations.
General information
Exposure date:junio 2001
Issue date:2001
Document language:English
Event:International Conference on Power Systems Transients (Rio de Janeiro, Brazil, 2001)
Origin:Instituto de Investigaciones Tecnológicas para Redes y Equipos Eléctricos (IITREE)